|
printable version
Basic maintenance of the cooling system
The service valve of the refrigerant tank
PERFORMANCE ORDER | 1. Before connecting the valve to the tank with coolant completely turn the knob counterclockwise. |  | 2. Turn the drain valve clockwise to the full. | 3. Remove the drain valve by hand clockwise to the full. Connect the center hose to the nozzle valve. | 4. In order to perforate the sealed container, turn the knob clockwise. |  | 5. To fill the central hose turn the knob clockwise to the full.
To fill the central hose turn the knob clockwise to the full. | 6. Loosen the nut of the hose attached to the central fitting manifold gauges. Vent. Then re-tighten the nut. |
| Installing the collector with pressure gauges A warning Fittings for the installation of a set of manifold gauges are mounted on the tubes of high and low pressure.
PERFORMANCE ORDER | 1. Close both manifold valves set with pressure gauges. | 2. Connect the low pressure hose to the high pressure nipple. | 3. Tighten hose nuts, but only by hand. |
|
Tightness test
After removing the air from the system, check for leaks.
PERFORMANCE ORDER | 1. Connect the full capacity of the refrigerant to the service valve. |  | 2. Open the valve of the high pressure refrigerant gas fueling system. | 3. On reaching the pressure gauge of low pressure 98 kPa (1 kg / cm 2) close the valve of high pressure. |  | 4. To check the tightness of the system use gas leak detector. If you find leaks and repair the faulty node or connection; then remove air from the system. |
|
Draining the system
Venting
Whenever the cooling system is connected to the atmosphere, it must be purged to remove moisture and air.
PERFORMANCE ORDER | 1. Connect a set of manifold gauges. | 2. Connect the central hose set of gauges to the input of the vacuum pump. |  | 3. Run the vacuum pump and open both valves. | | 4. When the low pressure gauge shows approximately 750 mmHg, close both valves and stop the vacuum pump. | 5. Check the constant pressure for at least 5 minutes. In case of change of pressure, check the tightness of the system and, if necessary, repair it. |  | 6. In the absence of leaks, disconnect the hose from the vacuum pump. |
| Charging
The functional test
After repairs are completed, perform the test of the air conditioning system to function in the following order.
|
|